This type of raised floor is only supplied with a top coat. It is usually antistatic. Often, the raised floor system is required by specification to be electrically conductive. To do this, a conductive PVC coating is glued onto the panel; all accessories involved in the current diversion circuit: protective edge, gasket, terminal, must be conductive. The current is diverted by means of grounding racks. The room must be grounded at least one rack for every 20 m²
Raised floors for data centers and server rooms are most often produced with an antistatic PVC coating. Industrial raised floors - panels with a thickness of 36mm, 38mm, or 40mm, standard dimensions are 600x600, but there are other panel sizes. Calcium sulphate panels are perfect for technical rooms. They are completely non-flammable and can be flame retardant for up to 60 minutes. Sulphate boards withstand heavy loads.
In the technical raised floor system, stringers and C-profiles can be found. The former are intended for the horizontal stability of the system and partly to increase the bearing capacity. C-profiles, as a rule, are used to increase the bearing capacity of the system, it is convenient to mount heavy equipment on them. The use of stringers or C-profiles is necessary when the height of the clean raised floor system is from 500mm.